lf

FS213

Electronic Flow Switch

Principle, Structure: There are two resistors in the enclosed probe based on the thermal principle. One of them is heated as the detection resistor and the other is not heated. As the reference resistance, when the medium flows, the heat on the heating resistor is taken away. The resistance value is changed, the two resistance differences are used as the basis for judging the flow rate.

Features: No moving parts, maintenance-free, easy to install, one type can meet a variety of diameter requirements. Switching value is continuously adjustable, very low pressure loss, compact structure, LED display flow trends and switch status.

Application: Gas-liquid dual-use type, used for pneumatic and hydraulic systems, circulating water, cutting fluid and lubricating oil flow monitoring, and pump idling protection.

Parameters

Setting Range1…150cm/s(Water), 3…300cm/s(Oil), 20…2000cm/s(Gas)Initializtion timeAbout 8s
Signal outputPNP, NPN, Relay Type, NO+NCElectrical protectionReverse, short circuit, overload protection
Power Supply24V±20%DCProtection levelIP67
Turn on currentMax 400mA (PNP, NPN);

Max 1A@24V ac/dc (Relay Type)

Medium temperature-20~80℃
No-load currentMax 80mAAmbient temperature-20~80℃
Flow indicationLED (6pcs)Storage temperature-20~80℃
Setting TypePotentiometer SettingConnection modeM12 Socket Connector
Proof Pressure Range100barMaterialProbe: stainless steel;

Housing: stainless steel

Medium temperature change≤4℃/sWeightAbout 0.4kg
Response time1–13s, Typical value 2s

Dimension

Dimension
Dimension