lf

LF58

LF58 Dual Pressure Switch for refrigeration system
-0.2 ~ 32bar

ModelPressure SideAdjustable rangeDifferentialFactory settingMax working pressure (Bar)
(Bar)(Bar)(Bar)
Min.Max.Min.Max.OFF(ON)ON(OFF)
LF5832Low-0.27.50.744220
High832Fixed 4201535
LF5832HMLow-0.27.50.74220
High832Fixed 420Manual Reset35
LF5832LMLow-0.2705Fixed 43Manual Reset20
High830Fixed 420Manual Reset35
MediumRefrigerant, Air, Water, Oil
Media Temperature-20 °C to 110 C
ConnectionM12X1.25, 7/16-20UNF – other connection types available on request
Contact ArrangementSPDT
Rated Voltage125VAC, 250VAC, 24VDC250VAC
Full Load Rated Amps20A, 10A, 8A50VA
Locked Roter Rated Amps72A, 72A, 64A4A

LF58 Dual pressure switches are usually used with fluorinated refrigerants to control the pressure of the compressor in the refrigeration system. It can also be used in air and water. It provides two pressure set points in one switch.

Several models are available with drip-proof enclosures for marine applications or explosion-proof enclosures for special applications.

Various contact functions are available. An internal Micro-switch ensures reliable switching. It is provided a standard Mounting Bracket