lf

40A Redundancy Type YSDR40

Support 1+1 and N+1 redundancy system
2 channels input and 1output
Suitable for redundancy operation of 12V/24V/48V system
Output current up to 40A
Cooling by free air convection
Built-in 2 channels DC OK signal and alarm relay contact
Installed on DIN Rail TS35/7.5 or 15

MODEL DETAIL SPEC.YSDR40-12YSDR40-24YSDR40-48
INPUTNUMBER OF INPUT:2 Channels
DC NORMAL VOLTAGE:12Vdc24Vdc48Vdc
DC VOLTAGE RANGE:9~14Vdc19~29Vdc36~60Vdc
RATED CURRENT:0~40A per input Continuous
VOLTAGE DROP (Vin-Vout) (max.):0.3V
PEAK CURRENT:0~60A per input  5Sec
EFFICIENCY (Typ.):98%
INPUT REVERSE CURRENT (max.):1mA
INPUT REVERSE VOLTAGE (max.):40Vdc40Vdc65Vdc
OUTPUTRATED CURRENT:0~20A,Continuous
PEAK CURRENT (max.):60A,5Sec
CAPACITANCE(Typ.):320uF
STANDBY POWER LOSSES(Typ.) :1.5W
PROTECTIONOVERLOAD:<60A,5Sec. No damage
SHORT CIRCUIT:<60A,5Sec. No damage
FUNCTIONREDUNDANCY:For 1+1 redundancy ,and support N+1 redundancy
BOTH INPUTS VOLTAGE ALARM:<8.5V or >14.7V (± 5% )<18V or >31V (± 5% )<34.2V or >63V (± 5% )
RELAY:30Vdc/1A resistive load
LED STATUS DISPLAY:Green LED OK
ENVIRONMENTCOOLING:Free air convection
WORKING TEMP.:-40 ~ +80 (Refer to “Derating Curve”)
WORKING HUMIDITY:5 ~ 95% RH non-condensing
STORAGE TEMP:-40 ~ +85℃
TEMP. COEFFICIENT:±0.03%/ ℃(0 ~ 60℃   )
VIBRATION:Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE:5000 meters/OVC II
SAFETY &EMSAFETY STANDARDS:IEC62368-1, UL62368-1, approved
WITHSTAND VOLTAGE:IP/OP – Chassis : 0.5KVac IP/OP- Relay : 0.5KVac Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE:IP/OP – Chassis, IP/OP- Relay, Relay – Chassis:>100M Ohms / 500Vdc / 25 / 70% RH
EMC EMISSION:BS EN/EN55032(CISPR32)Test Level / Note
EMC IMMUNITY:BS EN/EN61000-4-2,3,4,5,6,8
COTHERSMTBF:611.82K hrs min.    Telcordia SR-332 (Bellcore) ;     353.67K hrs min.   MIL-HDBK-217F (25 ℃ )
DIMENSION:55*125*102mm (W*H*D)
PACKING:0.35Kg;28psc/10.8Kg/1.24CUFT